Consistency Measurement – Medium Consistency Stock

Summary of the "Consistency Control Book" by G. Ostrost (1993)

Focus is on low consistency, but much of the material is still relevant.

  1. Hand Sampling:
  2. Five conditions for a sample tap and valve:

    1. It must extend into the process line beyond the pipe wall, at least 1/3 of pipe diameter.
    2. The tap inlet should be cut off parallel to the stock flow.
    3. It should be located in a turbulent area.
    4. Must be able to throttle the sample line without plugging it.
    5. Valve must shut off tight.

  1. On-line measurement

Light Based Sensors

But:

Mechanical Sensors

    1. They have a larger sensing area.
    2. They seem to be less affected by other variables than the blade is.

Gamma Radiation

But, the gamma unit:

  1. The Control System

Rule 1: Always design the consistency control system around the pump. It is a good mixer.

Rule 2: Always add dilution water close to the pump and at low velocity.

Rule 3: The stock chest must be well agitated.

Rule 4: Follow the manufacturer's recommendations on the piping run to the transmitter.

Rule 5: Mount the transmitter according to recommendations. With blade style units, this is critical. If a welding guide is supplied, ensure it is used. If a blade transmitter is installed on a horizontal run, put it on its side to avoid air.

Rule 6: Minimize dead time lag (2-6 seconds).

Rule 7: Always mount the control valve downstream from the transmitter.

Rule 8: The dilution header pressure must be constant. Make dilution header pressure only 10-15 psi greater than the maximum head in the stock chest. Usually it is too high.

Rule 9: The dilution piping should have minimum pressure drop.

Rule 10: The dilution valve should have a high resolution and rangeability. It should be a rotary valve with a high gain positioner (250).

The Dilution Valve

Control Mode

Tuning Objectives

    1. To be stable under all normal operating conditions.
    2. To hold setpoint as closely as possible.
    3. To return to setpoint as rapidly as possible after an upset.

¼ Amplitude Tuning

(Lambda tuning is best suited to process whose dead time lag is long compared to its time constant. Consistency control systems do not usually fall into that category".)

 

 

Tuning Procedures

    1. Adjust the process flow to the minimum.
    2. Put controller in manual (consistency).
    3. Make a step change in the dilution valve position, and time how long it takes to be seen on the transmitter. This is the dead time lag.
    4. Time how long it takes the consistency to reach a new stable point. 63% of this is the system time constant. Ideally, it should not be more than two times the dead time lag. If it is excessively long, check the system damping.
    5. Calculate the integral setting:
    6. If a digital system is used, and the sample interval is less than 1/5 of the dead time, then the previous equation can be used. If it is more, then:
    7. Adjust the proportional controller by trial and error to give the desired result.

Lambda tuning might be used effectively if Tc (time constant) is small.

Flow is the biggest problem in trying to tune a consistency loop. Every time the flow is cut in half, the gain of the system doubles.

  1. Special Systems

Recirculation on pressure control:

If large flow changes through the consistency control loop are required (3:1 or more), a recirculation system is the only way it can be done successfully!

Bypass/Sample System

Dual Pump Feed

In-Line Mixing

But:

Pulpers – Repulpers

Gravity Flow (From a Decker)

Hi Density Towers

Blow Tanks

  1. Transmitter Calibration

One-Point Calibration

Incremental Calibration

Bench Calibration

  1. New Concepts

Cascaded Systems:

Dilution Water Addition

Hi-D Towers